UPS ARES AR-MP10KS 10KVA/10KW ONLINE

UPS ARES AR-MP10KS 10KVA/10KW ONLINE

  • Power: 10KVA/10kW
  • Input voltage: 110Vac – 286Vac (full load)
  • Output voltage: 220V
  • Frequency: 50/60Hz (automatic reception)
  • Waveform: Standard sine wave
  • Connector: USB/RS232
  • System monitoring and control software (free)
  • parallel connection (optional)
  • Connect to load: Terminal block
  • Battery: 12V/9AH x 20
  • Power backup time can be extended by connecting to a battery cabinet
  • UPS size: R191*D460*C720 (mm)
  • Description
  • Tải tài liệu
  • Thông Số Kỹ Thuật

Description

General Features UPS ARES AR-MP10KS 10KVA/10KW ONLINE

  • Online double conversion with full digital control
  • Optimization battery group, the quantity of battery: 16/18/20pcs (Settable)
  • Wide input voltage range:110~286Vac
  • Input power factor 0.99 with PFC
  • Wide input frequency range
  • Selectable output voltage: 208/220/230/240Vac
  • Generator compatible
  • ECO mode operation for energy saving
  • Self-testing when UPS startup
  • Multiple communication interface:RS232/USB/EPO(Relay card /SNMP card optional)
  • Cold start
  • Design with maintenance switch (Optional)
  • Intelligent fan speed regulation
  • Multiple protection function:short-circuit,overload,overheat, battery overcharge and overdischarge,output low voltage and fan fault alarm

bộ lưu điện ares, bộ lưu điện 1kva online, bộ lưu điện 2kva online, bộ lưu điện 3kva online, bộ lưu điện 6kva online, bộ lưu điện 10kva online, bộ lưu điện 1 pha, bộ lưu điện 3 pha, ups lưu điện, bộ lưu điện offline, bộ lưu điện

Technical Specification

MODEL AR-MP10KH AR-MP10KS
Capacity 10000VA/ 10000W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Bypass voltage range Max.voltage:230~264Vac
Min.voltage:176~220Vac
OUTPUT
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
Output frequency Line Mode ±10% of the rated frequency
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:01
Harmonic distortion (THDv) ≤2% Linear load
≤5% Non linear load
Transfer time AC mode to Bat.Mode 0ms
Inverter to Bypass 5ms (Typical)
Output waveform Pure Sinewave
Overload Line Mode Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately
Bypass Mode 63A (Breaker)
Efficiency 93.50%
BATTERY
Battery voltage 192/216/240Vdc (Adjustable) ,without neutral 240Vdc
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max.current 8A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
LCD display Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
Battery voltage,Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337 ; S:191 x 460 x 720 (With wheel)
Net weight (kg) 13.5 71
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <58db at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8